Toxic Gas Sensors Model DM-700

Manufacturer: Teledyne| Detcon

Toxic Gas Sensors Model DM-700

Manufacturer: Teledyne| Detcon
Model 700 Series Sensors are a non-intrusive “Smart” sensors designed to detect and monitor oxygen and Toxic Gases in air using electrochemical sensor technology. 

The intelligent plug-in, field replaceable cell provides automatic recognition of gas type and range, and features over-sized gold-plated connections that help prevent corrosion. 

The Model 700’s rugged framework includes an intrinsically safe electro-polished 316 stainless steel housing with fully encapsulated electronics and dual layer surge protection. 

This innovative design virtually eliminates sensor failure due to water ingress, corrosion, vibration, and transient spikes. 

A primary feature of the Model 700 is embedded intuitive software that simplifies operator interface by guiding the user through routine calibration, configuration, and fault diagnostic functions using a built-in alpha/numeric display. 

The Model 700 is equipped with standard analog 4-20mA, and Modbus™ RS-485 outputs. Among its unique features is a wireless option that can be used with Detcon’s SmartWireless® product line. 

Additional integration options include a Remote Alarm Module (RAM) and HART. Detcon’s toxic gas and oxygen sensors have a long shelf life and are supported by an industry-leading warranty
Features
  • Failsafe User-Friendly Interface 
  • LED Display (With Antiglare Cover) 
  • Full Text Display Method 
  • Non-intrusive Interface 
  • Auto Zero/Auto Span 
  • Pre-emptive Fault Diagnostics Environmentally Bulletproof 
  • Electropolished 316SS Construction 
  • 100% Epoxy Encapsulated Circuitry 
  • Bulletproof I/O Protection 
  • Water-proof, Corrosion-Proof, Vibration-Proof Modular and Serviceable 
  • Modular Design 
  • Plug and Play Components 
  • Quick Thread Release Sensor Endcap (Allen Wrench only required) 
  • Integral Calibration Port

Specifications

Manufacturer

Sensor Type

  • Continuous diffusion/adsorption
  • 3-electrode electrochemical cell
  • Plug-in field replaceable Intelligent Type

Outputs

  • Linear 4-20 mA DC
  • RS-485 MODBUS-RTU

Electrical Classification

  • Explosion-proof CCSAUS Class I, Div. 1, Groups B, C, D () Class I, Zone 1, Group IIC

ATEX

  • II 2 G Ex d ib IIB + H2 T4 GB
  • Ingress Protection NEMA 4X, IP66

Safety Approvals

  • cCSAus
  • ATEX
  • CE Marking
  • SIL 2 Certified to IEC 61508

Dimensions

  • 7" H x 2.2" Dia.; 178 mmH x 65 mm Dia. (sensor assembly only)
  • 11" H x 6.1" W x 3.75" D; 280 mmH x 155 mmW x 96 mmD (with junction box)
  • Mounting holes (J-box) 5.5"; 140 mm center to center

Weight

  • 2 lb, 0.907 kg (sensor only)
  • 4 lb, 2.72 kg (with Aluminum J-Box)
  • 9 lb, 4.08 kg (with Stainless Steel J-Box)

Power Input

  • 11-30 Vdc

Power Consumption

  • Normal operation = 30 mA @ 24 V (< 0.75 watt)
  • Maximum = 50 mA @ 24 V (1.2 watts)

Inrush Current

  • 500 mA @ 24 V (typical)

RFI/EMI Protection

  • Complies with EN 50270

Analog Output

  • Linear 4-20 mA DC (1,000 ohms max loop load @ 24 Vdc)
  • 0 mA - All Fault Diagnostics
  • 2 mA In-Calibration
  • 4-20 mA 0-100 % Full Scale
  • 22 mA Over-range condition

Serial RS-485 Output

  • RS-485 Modbus RTU

Baud Rate

  • 9600 BPS (9600, N, 8, 1 Half Duplex)

Status Indicators

  • 4-digit LED display with gas concentration
  • Full-script menu prompts for AutoSpan,
  • Set-up Options, and Fault Reporting

Faults Monitored

  • Loop, Input Voltage, Missing Sensor, Zero, Processor, Memory, Calibration

Cable Requirements

  • Power/Analog 3-wire shielded cable Maximum distance is 13,300 ft with 14 AWG
  • Serial Output 2-wire twisted-pair with ground, shielded communication cable specifically for use with RS-485 installations Maximum distance is 4,000 ft to last sensor

I/O Protection

  • Over -voltage, Miswiring, EMI/RFI Immunity

  • Oil & Gas 
  • Chemical Plants 
  • Food & Beverage 
  • Steel Mills 
  • Pulp and Paper 
  • Refineries 
  • Wastewater Treatment Plants 
  • Utilities

show more