Combustible Gas Sensor FP-700
Manufacturer: Teledyne| DetconCombustible Gas Sensor FP-700
Manufacturer: Teledyne| DetconModel FP-700 is a non-intrusive “Smart” sensor designed to detect and monitor combustible gases in air over the range of 0-100% LEL using catalytic bead sensor technology.
The plug-in, field replaceable detector is poison-resistant and features over-sized gold-plated connections that help prevent corrosion.
The FP-700’s rugged framework includes an electro-polished 316 stainless steel housing with fully encapsulated electronics and dual layer surge protection.
This innovative design virtually eliminates sensor failure due to water ingress, corrosion, vibration, and transient spikes.
A primary feature of the Model FP-700 is embedded intuitive software that simplifies operator interface by guiding the user through routine calibration, configuration, and fault diagnostic functions using a built-in alpha/numeric display.
The Model FP-700 is equipped with standard analog 4-20mA, and Modbus™ RS-485 outputs. Among its unique features is a wireless option that can be used with Detcon’s SmartWireless® product line.
Additional integration options include a Remote Alarm Module (RAM), and HART. Detcon’s combustible gas sensor has an infinite shelf life and is supported by a 2-year warranty.
Features- LED Display (With Antiglare Cover)
- Full Text Display Method
- Non-intrusive Interface
- Auto Zero/Auto Span
- Pre-emptive Fault Diagnostics Environmentally Bulletproof
- Electropolished 316SS Construction
- 100% Epoxy Encapsulated Circuitry
- Bulletproof I/O Protection
- Water-Proof, Corrosion-Proof, Vibration-Proof Modular and Serviceable
- Modular Design
- Plug and Play Components
- Quick Thread Release (For Sensor Replacement)
- Integral Calibration Port
Specifications
Manufacturer
Sensor Type
- Continuous diffusion/adsorption
- Matched-pair catalytic bead detector
- Plug-in field replaceable
Sensor Life
- 3 to 5 years typical
Measurement Range
- 0-100% LEL (lower explosive limit)
Accuracy/Repeatability
- ±3% 0-50% LEL; ±5% 50-100% LEL
Response/Clearing Time
- T50 <10 seconds; T90 <30 seconds
Zero Drift
- <5% per year
Outputs
- Linear 4-20 mA DC
- RS-485 MODBUS-RTU
Electrical Classification
- Explosion proof
- cCSAus
- Class I, Division 1, Groups B, C, D (Tamb = -40°C to +75°C)
- Class I, Zone 1, Group IIB+H2
- ATEX
- II 2 G Ex d IIB + H2 T4 Gb (Tamb = -40°C to +70°C)
Ingress Protection
- NEMA 4X, IP66
Safety Approvals
- cCSus Performance to ANSI/ISA 60079-29-1
- (12.13.01)-2013 and CSA 22.2 #152
- ATEX
- CE Marking
- SIL2 Certified to IEC 61508
Warranty
- Plug-in detector - 2 years
- Transmitter - 2 Years
Operating Temperature Range
- -40°F to +167°F; -40°C to +75°C
Storage Temperature Range
- -40°F to +167°F; -40°C to +75°C
Operating Humidity Range
- 0-99% RH non-condensing
Dimensions
- 7”H x 2.2” Dia.; 178mmH x 65mm Dia. (sensor assembly only)
- 11”H x 6.1”W x 3.75”D; 280mmH x 155mmW x 96mmD (with junction box)
- Mounting holes (J-box) 5.5”; 140mm center to center
Weight
- 2 lbs; 0.907kg (sensor only)
- 6 lbs; 2.72kg (w/aluminum j-box)
- 9 lbs; 4.08kg (w/stainless steel j-box)
Power Input
- 11-30 VDC
Power Consumption
- Normal operation = 68mA (<1.7 watt)
- Maximum = 85mA (2 watts)
Inrush Current
- 1.0A @ 24V
RFI/EMI Protection
- Complies with EN50270
Analog Output
- Linear 4-20mA DC (1,000 ohms max loop load @ 24VDC)
- 0mA All Fault Diagnostics
- 2mA In-Calibration
- 4-20mA 0-100% full-scale
- 22mA Over-range condition
Serial RS-485 Output
- RS-485 Modbus™ RTU
Baud Rate
- 9600 BPS (9600,N,8,1 Half Duplex)
Status Indicators
- 4-digit LED display with gas concentration Full-script menu prompts for AutoSpan, Set-up Options, and Fault Reporting
Faults Monitored
- Operating Temperature, Loop, Input Voltage, Bridge Voltage, Zero, Sensor, Processor, Memory, Calibration
Cable Requirements
- Power/Analog 3-wire shielded cable Maximum distance is 13,300 feet with 14 AWG Serial Output 2-wire twisted-pair shielded cable specifically for use with RS-485 installations Maximum distance is 4,000 feet to last sensor
I/O Protection
- Over-voltage, Miswiring, EMI/RFI Immunity
- Oil and Gas Drilling Rigs
- Oil and Gas Production Sites
- Offshore Production Platforms
- FPSOs
- LNG/CNG Plants
- Refining and Petrochemical
- Pulp and Paper Mills