Explosion-Proof Strobe Light dSLB20 for Zone 1, 2, 21, 22
Manufacturer: EATON | FHFExplosion-Proof Strobe Light dSLB20 for Zone 1, 2, 21, 22
Manufacturer: EATON | FHFOptical signalling is often required for warning or notifying purposes in potentially explosive areas. The Ex II Strobe Light dSLB 20 provides suitable signalling for these purposes. It is designed for continuous operation and available for different operating voltages.
The dSLB 20 is activated by connecting the power supply. The sturdy housing of ingress protection IP 66/67 is suitable for both indoor and outdoor applications.
The Ex II strobe light has a small flameproof aluminium housing containing the electronics. The cap is made of hardened borosilicate glass. The terminal compartment is of protection type “increased safety”.
A signaling combination can be established using the provided stainless steel mounting plate with integrated junction box.
Features- Compact construction
- Versatile application
- Light intensity up to 15 joule
- Ingress protection IP 66/67
- Protection type: II 2 G Ex d e IIC T5, T6 Gb II 2 D Ex tb IIIC T95°C, T80°C Db
Specifications
Manufacturer
Protection type
- II 2 G Ex d e IIC T5, T6 Gb
- II 2 D Ex tb IIlC T95°C, T80°C Db
Approval
- PTB 99 ATEX 1028
- IECEx PTB 09. 0062
Housing
- Aluminium, surface varnished or powder-coated Housing colour Yellow/blue Cap Borosilicate glass dome with stainless steel protec
Housing colour
- Yellow/blue
Cap
- Borosilicate glass dome with stainless steel protection cage
Cap colour
- Transparent
- red
- amber
- green
- blue
Ingress protection
- IP 66/67 according to EN 60529
Protection class I
- I
Cable glands
- 1 x M20 x 1.5
- 1x blind plug M20 x 1.5
Connection terminals
- Terminal capacity: 2,5 mm² single-wire 1,5 mm² fine-wire
- Protective earth – Screw connection with wire protection clamp in connection enclosure max. 2.5 mm²
- Equipotential – Screw connection with wire bonding conductor protection clamp outside, cross section max. 4 mm²
Flash energy
- 5 joule/15 joule
Flash frequency
- Approx. 60/min. (1 Hz)
Average life cycle
- Approx. 5 x 106 flashes
Operating conditions
- Indoors
- Ourdoors
Operating position
- Any
Operating mode
- Continuous operation
Temperature range
- -55 °C bis +40 °C (T6)
- -55 °C bis +55 °C (T5)
Weight
- Approx. 2 kg