LIT25 Level Indicating Transmitter
Manufacturer: Pulsar MeasurementLIT25 Level Indicating Transmitter
Manufacturer: Pulsar MeasurementThe LIT25 is a level indication sensor that displays, controls, and transmits level.
The non-contacting level sensor mounts at the top of a tank and the compact, watertight display enclosure is mounted at a convenient location nearby.
Operators can calibrate the LIT25 with its 2-button keypad, without climbing to the top of the tank, enabling organizations to gain better stock and inventory control and tank level measurement that complies with health and safety regulations.
Use the built-in relay for level control or alarm, the large 4-digit display for local indication, and the isolated 4-20 mA output to transmit level to a PLC.
The standard ultrasonic level sensor measures liquid levels up to 9.8 m (32 ft) and includes automatic temperature compensation allowing for that all-important, reliable, level measurement even when conditions within the application are changing.
The optional all-Teflon sensor enables the LIT25 to provide level measurement for chemical applications and all ultrasonic sensors are available with optional intrinsic safety approvals for installation in hazardous rated locations.
Features- Low Cost
- Isolated 4-20 mA Output (1,000 ohm)
- Large LCD Display
- Programmable Signal Relay
- Non-Contacting Ultrasonic Sensor or Optional Pressure Sensor
- Built-in 2-Key Calibrator
- Watertight, Dust-tight Enclosure
Specifications
Manufacturer
Electronics Enclosure
- NEMA 4X (IP66) Polycarbonate with Clear, Shatterproof Cover
Accuracy
- ± 0.25 % of Range or 2 mm (0.08 in), whichever is greater
Display
- Large 19 mm (0.75 in) High, 4-Digit LCD
Power Input
- 100-130 Vac 50/60 Hz, 5 W Max.
Outputs
- Isolated 4-20 mA, 1,000 ohm Load Max.
Signal Relay
- 1 Relay, Rated 120-240 Vac or 24 Vdc, 1 A, Programmable for Level Alarm, Echo Loss Alarm, Pump Control, or Temperature Alarm
Temperature Compensation
- Temperature Probe Inside the Level Sensor for High Accuracy in Changing Temperatures
Exposed Material
- PVC & Teflon
Operating Temperature
- -25° to 60° C (-13° to 140° F)
- Chemical Applications
- Hazardous Rated Locations