DG-TX7 Intelligent Flammable Gas Detector
Manufacturer: Teledyne| DetconDG-TX7 Intelligent Flammable Gas Detector
Manufacturer: Teledyne| DetconThe MultiXplo DG-TX7 intelligent catalytic based flammable gas detector is used to detect a wide range of gases, including hydrogen (H2).
The device has been designed for ease of installation, operation and maintenance in testing environments.
The DG-TX7 employs a pair of OXYCOL catalytic sensors in a compensated circuitry in order to provide reliable flammable gas detection in harsh environments, as long as oxygen is present.
The intelligent, microprocessor driven unit is fully configurable using a wireless handheld terminal (TLU) or optionally via HART giving true flexibility to the installer.
Parameters such as relay operation and alarm levels are all set via the TLU, hazardous area approved handheld unit.
In addition, the sensor element is protected by the onboard electronics to prevent exposure to over-range LEL gas concentrations. This helps reduce ongoing maintenance and service costs.
The user can select between 4-20 and 0-22 mA depending on system requirements.
The unit may be interfaced directly with a wide range of panels, controllers and PLC’s etc.
Device status, including measured gas level is indicated on a color coded 4 digit LED display.
Specifications
Manufacturer
Accuracy
- ± 5 % of Full Scale Deflection
Approvals & Certifications
- ATEX - II 2 G Ex d IIC T6 Gb (-40° to 65° C)
- IEC Ex d IIC T6 Gb, LCl 11.0060X
- ISO 9001: 2008
Communication
- HART
Consumption
- 4 W Normal
Display
- 4-Digit LED Display & Backlight Color Status
Electrical Connectors
- 16 AWG (1.5 mm²)
- 28 AWG, (0.14 mm²)
- Shielded Cable
Enclosure, Body Material
- 316L Stainless Steel
Environmental Protection
- IP66
Humidity
- 0 to 95 % Relative Humidity, Non-Condensing
Load Impedance
- 700 ohms
Measuring Range
- 0 to 100 % Lower Explosive Limit (LEL)
Media
- Gas
Operating Temperature
- -40° to 65° C (-40° to 149° F)
Output
- 4-20 mA
Power Requirement
- 18-28 Vdc
Relay Output
- 1 A / 30 V
Repeatability
- ± 1 % of Full Scale Deflection
Response Time
- T90 < 15 seconds (Methane)
RFI/EMI Protection
- Complies with EN 50270
Span & Zero Effect
- ± 3 % of Full Scale Deflection - Zero Drift
Storage Temperature
- -40° to 70° C (-40° to 158° F)
- Chemical Plants
- Offshore Drilling & Production Platforms
- Processing & Storage Plants
- Refineries