SIMTRONICS Multi-Spectrum UV/2IR Flame Detector
Price
Request a Quote
Stock
Contact for current lead time
UV/2IR 57° Veritcal 120° Horizontal
Specifications
Manufacturer
Output Signal
- Standard: 4-20 mA or 0-22 mA
- Alarms: 2 Configurable Relays, Max. 1 A/ 30 Vcc
- Visual: Normal Operating, Alarm, or Fault
Operating Temperature
- -40° C to +65° C
Ingress
- IP66
Approvals & Certifications
- SIL: SIL 3 without redundancy according to IEC 61508-1 to 7
- ATEX: II 2 G Ex d IIC T6 Gb
- IECEx: IEC 60079-0 / IEC 60079-1
- CE DPC: According to EN 54-10: 2002 + A1: 200